Tiêu chuẩn quốc tế

Số hiệu

Standard Number

ASTM F1883-03(2013)
Năm ban hành 2013

Publication date

Tình trạng W - Hết hiệu lực

Status

Tên tiếng Anh

Title in English

Standard Practice for Selection of Wire and Cable Size in AWG or Metric Units
Chỉ số phân loại Quốc tế (ICS)

By field

29.060.01 - Dây và cáp điện nói chung
Số trang

Page

3
Giá:

Price

Liên hệ / Contact us
Phạm vi áp dụng

Scope of standard

1.1 This practice is intended as a guide to shipbuilders, shipowners, and design agents for use in the selection of conductor size for single conductor or multiple conductor cable sizes either in American Wire Gauge (AWG) or metric designations for commercial ship design and construction.

1.2 The comparison chart of electrical conductor sizes shown in Table 1 presents a combined listing of international standard sizes of Class 2 stranded copper conductors in accordance with AWG (Specification B8) English units or IEC (IEC 60228) metric units.

TABLE 1 Conversion Table-AWG/Metric Preferred Sizes of Conductors

A Ampacity of single-conductor cable in air at ambient temperature of 30°C and maximum conductor temperature not exceeding 60°C.B Temperature correction: the conductor resistance may be corrected for moderate temperature differences from the noted reference temperature by the following equation. The parameter, αT, varies with conductivity and temperature. For a list of common temperature coefficients see Test Methods B193.

C An asterisk (*) indicates preferred sizes for wires of American Wire Gauge or per IEC 60228 (metric) as appropriate.

1.3 As a precautionary caveat, some conductor sizes listed in Table 1 may exceed minimal size requirements of the U.S. Coast Guard, the American Bureau of Shipping, and IEEE STD 45 for specific applications.

1.4 The values stated for ampacity and dc resistance are presented as maximum values and are provided for information only.