Tiêu chuẩn quốc tế

Số hiệu

Standard Number

IEC 62271-110:2023
Năm ban hành 2023

Publication date

Tình trạng A - Còn hiệu lực

Status

Tên tiếng Anh

Title in English

High-voltage switchgear and controlgear – Part 110: Inductive load switching
Thay thế cho

Replace

IEC 62271-110:2018
Chỉ số phân loại Quốc tế (ICS)

By field

29.130.10 - Cơ cấu chuyển điện áp cao và cơ cấu điều khiển
Số trang

Page

66
Giá:

Price

Liên hệ / Contact us
Phạm vi áp dụng

Scope of standard

This part of IEC 62271 is applicable to AC switching devices designed for indoor or outdoor installation, for operation at frequencies of 50 Hz and 60 Hz on systems having voltages above 1 000 V and applied for inductive current switching. It is applicable to switching devices (including circuit-breakers in accordance with IEC 62271-100) that are used to switch high-voltage motor currents and shunt reactor currents and also to high-voltage contactors used to switch high-voltage motor currents as covered by IEC 62271-106.

Switching unloaded transformers, i.e. breaking transformer magnetizing current, is not considered in this document. The reasons for this are as follows:

a) Owing to the non-linearity of the transformer core, it is not possible to correctly model the switching of transformer magnetizing current using linear components in a test laboratory. Tests conducted using an available transformer, such as a test transformer, will only be valid for the transformer tested and cannot be representative for other transformers.

b) As detailed in IEC TR 62271-306, the characteristics of this duty are usually less severe than any other inductive current switching duty. Such a duty can produce severe overvoltages within the transformer winding(s) depending on the re-ignition behaviour of the switching device and transformer winding resonance frequencies.

NOTE 1 The switching of tertiary reactors from the high-voltage side of the transformer is not covered by this document.

NOTE 2 The switching of shunt reactors earthed through neutral reactors is not covered by this document. However, the application of test results according to this document, on the switching of neutral reactor earthed reactors (4-leg reactor scheme), is discussed in IEC TR 62271-306.